Products

Product Overview

ZXDU68 B301 V6.0 Embedded Power System

ZXDU68 B301 V6 is an 8U height, 19-inch width embeded power system. The system can provide power to -48 V series communication equipment, can charge for batteries. When fully configured, the system is equipped with six rectifiers (can mix insert solar PU) and can provide a maximum output power of 18kW

Highlights:

  • Rectifier with peak efficiency up to 97%, in the sleep mode, the output power of the rectifier is lower than 4W.  
  • High power density up to 49.2W/in, making optimum space utilization.  
  • 80V~300V wide input voltage, high adaptive to poor grid to protect battery.  
  • The system can be remotely managed through a computer installed with Web explorer anywhere if Ethernet is available.  
  • Storage expansion through the USB interface, realize fast roll-out by batched configuring site information. 
  •  Rectifier easy touch function enables operator of convenient communication between CSU and multiple rectifiers.  
  • Providing dry contacts, RJ45, RS232, and RS485 interfaces. Meeting the requirements of HTTPS, SNMP networking to save maintenance and initial investment.  
  • Rectifier and controller module hot-swappable
Learn more
Product_Parameter
Model Parameter(Operator) Parameter(Enterprise)
Model Type ZXDU68 B301 V6.0
Rectifier module ZXEPS R4850F1  
CSU module CSU602A  
AC input  
Input type 220/380VAC, three-phase five-wire (L1/L2/L3/N/PE)  
Input voltage range 80VAC~300VAC  
Frequency 45~66Hz, 50/60Hz  
Input power factor ≥0.99  (50%-100% load)  
AC input 1 × 63 A/3P  
AC output    
Option 1 including one AC output circuit breaker and one three-hole socket  
Option 2 including one AC output circuit breaker and Neutral wire connection terminal  
AC SPD Class C, Imax=40kA(8/20μS)  
DC output  
Output power Maximum 18kW   
Output voltage -53.5 V (-42V ~ -59.5V adjustable)
Module capacity 6 PCS  
Module efficiency Rectifier: ≥95.5% (under rated Load), Peak efficiency is 97%  
Load distribution Standard configuration 12P, maximum 20P  
Battery distribution 4×125A/1P MCBs   
Operation environment  
Operation temperature -40℃~+70℃,  
Storage temperature -45℃~+75℃  
Humidity 5% ~ 95%  
Altitude 0 to 2000 m: 100% output power; 2000 to 3000 m: The power derating percentage is 1% when the altitude increases by 100 m. Customer shall use system under derating consideration.  
Structure  
Dimension 3mm × 482 mm × 360 mm(H × W × D)  
Weight Chassis weight: 20.5kg (not including rectifiers)  
Standard  
Safety IEC62368; GB4943  
EMC IEC61000  